site modificado para site do tecnico

manual spectra 1728/1738

Contactos




 
site modificado para site do tecnico



  ContactosSpectra 1759MG - 1 - Programming Guide
1759MG
System Programming Guide
Software Version 2.0
Default Installer Code
0000 / 000000 (see section [281] on page 18)
Default System Master Code
1234 / 123456 (see section [301] on page 18)
How Do I Enter Programming Mode?
1)Press [ENTER].
2)Enter your [INSTALLER CODE].
3)Enter 3-digit [SECTION] you wish to program.
4)Enter required [DATA].
Decimal and Hexadecimal Programming Table
Trouble Display
Press the [TBL] or [TRBL] key to view the Trouble Display. Please note that the keypad can be programmed to emit a BEEP every 5 seconds whenever a new trouble condition has occurred. Press the [TBL] or [TRBL] key to stop the beeping.
[1] - No Battery or Low Battery[8] - Timer Loss**
[2] - Wireless Transmitter Low Battery[9] - Tamper or Zone Wiring Failure*
[3] - Power Failure[10] - Telephone Line Monitoring Failure
[4] - Bell Output Disconnected[11]/[STAY] - Fire Loop Trouble*
[5] - Maximum Bell Current[12]/[BYP] - Module Loss
[6] - Maximum Auxiliary Current[13]/[MEM] - Wireless Transmitter Supervision Loss*
[7] - Communicator Report Failure[16]/[FORCE] and [TBL]/[TRBL] flashes - Keypad Fault
* Press the illuminated key ([9], [STAY] or [MEM]) to view which zones are causing the trouble. Enter the Installer Code to clear Tamper troubles.
** Press [8] to re-program the time.
Value or Action
What Do I Press?
What Do I See?
10-Zone LED
16-Zone LED
LCD
Values 1 to 9 [1]
to [9] [1]
to [9]
[1] to [9]
[1] to [9]
A (hex only) [0] [0 (10)]
[10]
0
B (hex only) [
STAY] [
STAY]
[11]
B
C (hex only) [
BYP] [
BYP]
[12]
C
D (hex only) [
MEM] [
MEM]
[13]
D
E (hex only) [
TBL] / [TRBL] [
TBL]
[14]
E
F (hex only) [
PG] / [FNC1] [
PG]
[15]
F
Exit Without Saving [
CLEAR]
[ENTER] flashes
[ARM1] & [STAY1] flash
“SECTION [ ]”
Erase Current Digit [
FORCE]
Displays next digit or next section
Save Data (hex only) [
ENTER]
Advances to the next section

Spectra 1759MG - 3 - Programming Guide
Table of Contents
Default Installer Code.................................................................................................................................................. 1
Default System Master Code ...................................................................................................................................... 1
How Do I Enter Programming Mode? .......................................................................................................................... 1
Decimal and Hexadecimal Programming Table........................................................................................................... 1
Trouble Display ........................................................................................................................................................... 1
Data Display Mode (LED Keypads Only) ..................................................................................................................... 5
Configuring the 1686H, 1686V and 1689 Keypads (V2.0 or higher) ............................................................................ 5
Zone Programming...................................................................................................................................................... 6
System Timers ............................................................................................................................................................ 8
Programmable Outputs ............................................................................................................................................... 9
System Options ......................................................................................................................................................... 12
Communication Settings ........................................................................................................................................... 15
Report Codes ............................................................................................................................................................ 16
System Settings ........................................................................................................................................................ 18
User Code Options.................................................................................................................................................... 18
Reprogram All Modules............................................................................................................................................. 19
Paradox Memory Key (PMC-3) ................................................................................................................................. 19
4-PGM Output Modules V2.0 ..........................................................................................................20
PGM Programming.................................................................................................................................................... 20
Printer Module V2.0.........................................................................................................................21
PGM Programming.................................................................................................................................................... 22
Clock Programming................................................................................................................................................... 22
Voice-assisted Arm/Disarm Bus Module V2.0 ..............................................................................23
Wireless Features...........................................................................................................................24
Zone Assignment ...................................................................................................................................................... 24
Serial Number Display............................................................................................................................................... 24
Signal Strength Display ............................................................................................................................................. 24
Remote Control User Assignment............................................................................................................................. 25
Button Options........................................................................................................................................................... 25
Remote Control Assignment ..................................................................................................................................... 26
Zone Expansion Bus Modules .......................................................................................................27
PGM Programming (SPC-ZX8 and APR3-ZX8 Only) ................................................................................................ 27
User Operation ...............................................................................................................................28
Partitioning ................................................................................................................................................................ 28
Programming Access Codes..................................................................................................................................... 28
Programming Chime Zones ...................................................................................................................................... 29
Keypad Muting .......................................................................................................................................................... 29
Keypad Backlight (1686H and 1686V Only)............................................................................................................... 29
Installer Function Keys.............................................................................................................................................. 29
Appendix A - Ademco CID Report Code List (Prog.) ...................................................................30
Appendix B - Ademco CID Report Code List (All Codes)............................................................31
Bus Module Connections ...............................................................................................................32
Printer Module (APR3-PRT1).................................................................................................................................... 32
4-PGM Output Module (APR3-PGM4) ...................................................................................................................... 33
4-zone expansion Bus Module (SPC-ZX4 and APR3-ZX4) ...................................................................................... 33
Spectra 1759MG - 4 - Programming Guide
Voice-assisted Arm/Disarm Bus Module (APR3-ADM2)............................................................................................ 34
8-Zone Expansion Bus Modules (SPC-ZX8 and APR3-ZX8) ................................................................................... 35
Hardware Connections................................................................................................................... 36
Single Zone Inputs .................................................................................................................................................... 36
Connecting Fire Circuits, Keyswitches and PGMs..................................................................................................... 36
Programming a Wireless Fire Zone ........................................................................................................................... 36
Alarm Relay and PGM Connections .......................................................................................................................... 37
Connecting More Than Two Keypads........................................................................................................................ 37
AC Power & Backup Battery Connections ................................................................................................................. 37
Spectra 1759MG PCB Layout................................................................................................................................... 38
Spectra 1759MG - 5 - Programming Guide
Data Display Mode (LED Keypads Only)
View the section’s programming one digit at a time. Does not function with sections using Feature Select Programming.
Configuring the 1686H, 1686V and 1689 Keypads (V2.0 or higher)
The keypad’s zone number, EOL definition and anti-tamper switch are programmed through the keypad’s programming mode. To do so:
PLEASE NOTE: After two minutes, the keypad exits programming mode.
Key [1] - Keypad Zone Selection
Key [1] determines whether the keypad’s zone is Keypad Zone 1 or Keypad Zone 2. When key [1] is OFF (not illuminated), the keypad’s zone is Keypad Zone 1. When key [1] is ON (illuminated), the keypad’s zone is Keypad Zone 2. Refer to the Zone Recognition Table on page 6 for more information.
Key [1] OFF - Keypad Zone 1 (default)
Key [1] ON - Keypad Zone 2
Key [2] - EOL Definition
Key [2] determines the keypad zone’s EOL definition. When key [2] is OFF (not illuminated), EOL is disabled and the keypad zone uses the on-board EOL resistor. When key [2] is ON (illuminated), EOL is enabled and the keypad zone requires that an external EOL resistor be connected (refer to Spectra 1759MG PCB Layout on page 38 for more details).
Key [2] OFF - EOL disabled
Key [2] ON - EOL enabled (default)
Key [3] - On-Board Tamper
Key [3] enables or disables the keypad’s on-board anti-tamper switch. When key [3] is OFF (not illuminated), the anti-tamper switch is disabled. When key [3] is ON (illuminated), the anti-tamper switch is enabled.
Key [3] OFF - On-board anti-tamper switch disabled
Key [3] ON - On-board anti-tamper switch enabled
PLEASE NOTE: The keypad can be ordered with or without an anti-tamper switch. If the keypad has no anti-tamper switch, key [3] will be OFF by default. If the keypad has an anti-tamper switch, key [3] will be ON by default.
How Do I Configure The Keypad?
1)Press [ENTER]
2)Enter your [INSTALLER CODE] (default: 0000 / 000000)
3)Press the [PG] (1686H/V) / [FNC1] (1689) key and hold it for 3 seconds.
4)Press the desired key ([1] to [3]. See below)
5)Press [ENTER] to exit programming mode
To access the Data Display Mode, press the [ENTER] key after entering a section and before entering any data. The three LEDs as indicated below will begin to flash indicating that you are in the Data Display Mode.Each time the [ENTER] key is pressed, the keypad will display the next digit in the current section and will continue through all the following sections one digit at a time without changing the programmed values. Not available for sections using the Multiple Feature Select Method. Press the [CLEAR] key at any time to exit the Data Display Mode.
Spectra 1759MG - 6 - Programming Guide
Zone Programming
When programming zones, the zone assignments are dependent on where the detection devices are connected to in the system (see Zone Recognition Table). In installations that require using mostly the expansion inputs, refer to Reassign Keypad Zone 2 (see section [126] option [7] on page 12) and Reassign zones to expansion inputs (see section [126] option [8] on page 12).
.
Do not assign inputs from different modules to the same expansion input.
Zone Recognition Table
Option [7]: OFF
Option [8]: OFF
Option [7]: ON
Option [8]: OFF
Option [7]: OFF
Option [8]: ON
Option [7]: ON
Option [8]: ON
Control Panel
Input 1 =
Zone 1
Zone 1
Zone 1
Zone 1
Input 2 =
Zone 2
Zone 2
Zone 2
Zone 2
Input 3 =
Zone 3
Zone 3
N/A
N/A
Input 4 =
Zone 4
Zone 4
N/A
N/A
Input 5 =
Zone 5
Zone 5
N/A
N/A
Keypad
Zone 1 =
Zone 6
Zone 6
Zone 3
Zone 3
Zone 2 =
Zone 7
N/A
Zone 4
N/A
Expansion
Input 1 =
Zone 8
Zone 7
Zone 5
Zone 4
Input 2 =
Zone 9
Zone 8
Zone 6
Zone 5
Input 3 =
Zone 10
Zone 9
Zone 7
Zone 6
Input 4 =
Zone 11
Zone10
Zone 8
Zone 7
Input 5 =
Zone 12
Zone 11
Zone 9
Zone 8
Input 6 =
Zone 13
Zone 12
Zone 10
Zone 9
Input 7 =
Zone 14
Zone 13
Zone 11
Zone 10
Input 8 =
Zone 15
Zone 14
Zone 12
Zone 11
= not displayed on 10-Zone LED Keypads
Option [7]
= Reassign Keypad Zone 2
Option [8]
= Reassign zones to expansion inputs
Spectra 1759MG - 7 - Programming Guide
Only the control panel’s on-board inputs can be defined as a Fire, Delayed Fire or a Keyswitch zone.
The on-board zones are zones 01 to 05. To program a wireless fire zone, refer to Programming a Wireless Fire Zone on page 36.
How Do I Program the Zones?
1)Press the [ENTER] key
2)Enter the [INSTALLER CODE] (Default: 0000 / 000000)
3)Enter 3-digit [SECTION]
4)Enter one digit from the Zone Definition table (see page 7)
5)Enter one digit from the Partition Assignment table (see page 7)
6)Select one or more options from the Zone Options table (see page 7)
7)Press the [ENTER] key
Section
Description
Zone
Definition
Partition
Assignment
Zone Options
[001] = Zone 01:
1 2 3 4 5 6 7 8
[002] = Zone 02:
1 2 3 4 5 6 7 8
[003] = Zone 03:
1 2 3 4 5 6 7 8
[004] = Zone 04:
1 2 3 4 5 6 7 8
[005] = Zone 05:
1 2 3 4 5 6 7 8
[006] = Zone 06:
1 2 3 4 5 6 7 8
[007] = Zone 07:
1 2 3 4 5 6 7 8
[008] = Zone 08:
1 2 3 4 5 6 7 8
[009] = Zone 09:
1 2 3 4 5 6 7 8
[010] = Zone 10:
1 2 3 4 5 6 7 8
[011] = Zone 11:
1 2 3 4 5 6 7 8
[012] = Zone 12:
1 2 3 4 5 6 7 8
[013] = Zone 13:
1 2 3 4 5 6 7 8
[014] = Zone 14:
1 2 3 4 5 6 7 8
[015] = Zone 15:
1 2 3 4 5 6 7 8
Defaults =
Empty
Partition 1
1 and 2 ON
[FORCE] key = emptyZone DefinitionEmpty - Zone Disabled1 - Entry Delay 12 - Entry Delay 23 - Follow4 - Instant5 - 24Hr Burglary6 - 24Hr BuzzerAdditional definitions for on-board terminals:7 - Keyswitch8 - Fire 24Hr9 - Delayed Fire 24HrPartition AssignmentEmpty - Zone Disabled1 - Partition 12 - Partition 23 - Both PartitionsZone Options1 - Auto Zone Shutdown2 - Bypass Enabled3 - Stay Zone4 - 5 - Zone Alarm TypeoffoffAudible alarm (steady)offonAudible alarm (pulsed)onoffSilent alarmononGenerates a report only6 - Intellizone7 - Delay alarm transmission8 - Force ZoneKeyswitch Options1 - off = Maintainedon = Momentary2 - off = Regular Armon = Stay ArmSecond DigitFirst Digit
Spectra 1759MG - 8 - Programming Guide
System Timers
Section #
Decimal Value (000 to 255)
Description
Default
[050]
___/___/___
x 10 msec.
ZONE SPEED (ZONE 1)
600 msec.
[051]
___/___/___
x 10 msec.
ZONE SPEED (ZONE 2)
600 msec.
[052]
___/___/___
x 10 msec.
ZONE SPEED (ZONE 3)
600 msec.
[053]
___/___/___
x 10 msec.
ZONE SPEED (ZONE 4)
600 msec.
[054]
___/___/___
x 10 msec.
ZONE SPEED (ZONE 5)
600 msec.
[055]
___/___/___
x 10 msec.
ZONE SPEED (ZONE 6)
600 msec.
[056]
___/___/___
x 10 msec.
ZONE SPEED (ZONE 7)
600 msec.
[057]
___/___/___
x 10 msec.
ZONE SPEED (ZONE 8)
600 msec.
[058]
___/___/___
x 10 msec.
ZONE SPEED (ZONE 9)
600 msec.
[059]
___/___/___
x 10 msec.
ZONE SPEED (ZONE 10)
600 msec.
[060]
___/___/___
x 10 msec.
ZONE SPEED (ZONE 11)
600 msec.
[061]
___/___/___
x 10 msec.
ZONE SPEED (ZONE 12)
600 msec.
[062]
___/___/___
x 10 msec.
ZONE SPEED (ZONE 13)
600 msec.
[063]
___/___/___
x 10 msec.
ZONE SPEED (ZONE 14)
600 msec.
[064]
___/___/___
x 10 msec.
ZONE SPEED (ZONE 15)
600 msec.
[065]
FUTURE USE
[066]
___/___/___
seconds (000 = follow Deactivation Event)
PGM1 TIMER
5 sec.
[067]
___/___/___
seconds (000 = follow Deactivation Event)
PGM2 TIMER
5 sec.
[068]
___/___/___
seconds (000 = follow Deactivation Event)
GLOBAL PGM TIMER
5 sec.
[069]
___/___/___
seconds
ENTRY DELAY 1
45 sec.
[070]
___/___/___
seconds
ENTRY DELAY 2
45 sec.
[071]
___/___/___
seconds
EXIT DELAY 1
30 sec.
[072]
___/___/___
seconds
EXIT DELAY 2
30 sec.
[073]
___/___/___
minutes (000 = no bell on alarm)
BELL CUT-OFF TIMER (PARTITION 1)
4 min.
[074]
___/___/___
minutes (000 = no bell on alarm)
BELL CUT-OFF TIMER (PARTITION 2)
4 min.
[075]
___/___/___
x 15 minutes (000 = disabled)
NO MOVEMENT TIMER (PARTITION 1)
Disabled
[076]
___/___/___
x 15 minutes (000 = disabled)
NO MOVEMENT TIMER (PARTITION 2)
Disabled
[077]
___/___/___
seconds (minimum 10 sec.)
ANSWERING MACHINE OVERRIDE DELAY
Disabled
[078]
___/___/___
(000 = no answer, maximum = 15 rings)
NUMBER OF RINGS
8 rings
[079]
___/___/___
x 2 sec. (minimum 32 sec.)
TLM FAIL TIMER
32 sec.
[080]
___/___/___
seconds
DELAY ALARM TRANSMISSION
Disabled
[081]
___/___/___
(000 = 16, maximum = 16)
MAXIMUM DIALING ATTEMPTS
8 attempts
[082]
___/___/___
seconds
DELAY BETWEEN ATTEMPTS
20 sec.
[083]
___/___/___
seconds
PAGER DELAY
5 sec.
[084]
___/___/___
seconds (minimum 10 sec.)
INTELLIZONE DELAY
48 sec.
[085]
___/___/___
seconds
RECENT CLOSING DELAY
No delay
[086]
___/___/___
minutes
POWER FAILURE REPORT DELAY
15 min.
[087]
___/___/___
days (000 = disabled)
AUTO TEST REPORT
Disabled
[088]
___/___/___
000 to 127 = +1 to +127 seconds
128 to 255 = -1 to -127 seconds
CLOCK ADJUST
Disabled
[089]
___/___/___
(000 = disabled, maximum = 15)
AUTO ZONE SHUTDOWN COUNTER
5
[090]
___/___/___
minutes (000 = disabled)
RECYCLE ALARM DELAY
Disabled
[091]
___/___/___
(000 = disabled)
RECYCLE ALARM COUNTER
Disabled
[092]
___/___/___
attempts before locking (000 = disabled)
KEYPAD LOCKOUT
Disabled
[093]
___/___/___
minutes (000 = disabled)
KEYPAD LOCKOUT DELAY
Disabled
[094]
___/___/___
seconds (000 = disabled)
PANIC LOCKOUT TIMER
Disabled
[095]
___/___/___
days (000 = disabled)
CLOSING DELINQUENCY TIMER (PARTITION 1)
Disabled
[110]
___/___ : ___/___ hours (00 to 23) : minutes (00 to 59)
___/___ : ___/___ hours (00 to 23) : minutes (00 to 59)
___/___ : ___/___ hours (00 to 23) : minutes (00 to 59)
AUTO TEST REPORT (TIME OF DAY)
Disabled
[111]
AUTO-ARM TIME (PARTITION 1)
Disabled
[112]
AUTO-ARM TIME (PARTITION 2)
Disabled
Spectra 1759MG - 9 - Programming Guide
Programmable Outputs
Each PGM Deactivation event can be used as another start (activation) event if their respective PGM timer (see sections [066] to [068]) is programmed with a value other than 000.
Example: section [120] = 05 03 02: this means PGM1 will activate whenever partition 2 is Stay Armed.
Section #
Event Group #
Sub-Group #
Partition #
[120]
PGM 1 PGM Activation Event
___/___
___/___
___/___
[121]
PGM 1 PGM Deactivation Event
___/___
___/___
___/___
[122]
PGM 2 PGM Activation Event
___/___
___/___
___/___
[123]
PGM 2 PGM Deactivation Event
___/___
___/___
___/___
[124]
Global PGM Activation Event
___/___
___/___
___/___
[125]
Global PGM Deactivation Event
Used to activate PGMs on expansion modules & LCD keypads.
___/___
___/___
___/___
Event Group #
Sub-Group #
00 = Zone OK
01 to 15 = Zones 1 to 15
99 = Any Zone
01 = Zone Open
01 to 15 = Zones 1 to 15
99 = Any Zone
02 = Partition Status
00 = System not ready (Partition 1 only)
01 = System ready (Partition 1 only)
02 = Steady Alarm in Partition
03 = Pulsed Alarm in Partition
04 = Pulsed or Steady Alarm in Partition
05 = Alarm in Partition Restored
06 = Bell Squawk Activated (Partition 1 only)
07 = Bell Squawk Deactivated (Partition 1 only)
08 = Ground start (Partition 1 only)
09 = Disarm Partition
10 = Arm Partition
11 = Entry Delay (breach when system is armed)
99 = Any Sub-Group
05 = Non-Reportable Events
00 = Telephone Line Trouble (Partition 1 only)
01 = [PG] or [FNC1] key was pressed (Partition 1 only). This
option can also be used to reset smoke detectors.
02 = Instant Arming
03 = Stay Arming
04 = Force Arming
05 = Fast Exit (Force & Regular Only)
06 = PC Fail to Communicate (Partition 1 only)
07 = Midnight (Partition 1 only)
99 = Any Sub-Group (Partition 1 only, except 02 to 05)
06 = Arm/Disarm with Remote Control
01 to 08 = Remote Controls 1 to 8
99 = Any Remote Control
07 = Button Pressed on Remote
(see button option “B” on page 25)
01 to 08 = Remote Controls 1 to 8
99 = Any Remote Control
08 = Button Pressed on Remote
(see button option “C” on page 25)
01 to 08 = Remote Controls 1 to 8
99 = Any Remote Control
01 = Partition 102 = Partition 299 = Any PartitionThe Sub-Groups proceeded by “(Partition 1)” cannot be assigned to activate Partition 2.
Spectra 1759MG - 10 - Programming Guide
09 = Button Pressed on Remote
(see button option “D” on page 25)
01 to 08 = Remote Controls 1 to 8
99 = Any Remote Control
10 = Bypass Programming
01 to 48 = User Code Numbers 001 to 048
99 = Any User Code
11 = User Activated PGM
01 to 48 = User Code Numbers 001 to 048 (Partition 1 only)
99 = Any User Code
12 = Zone with Delay Transmission Option Enabled is Breached
01 to 15 = Zones 1 to 15
99 = Any Zone
13 = Arm with User Code
01 to 48 = User Code Numbers 001 to 048
99 = Any User Code
14 = Special Arm
00 = Auto Arming (timed/no movement)
01 = Late to Close (Auto-Arming failed)
02 = No Movement Auto-Arming
03 = Partial Arming (Stay, Force, Instant, Bypass)
04 = One-Touch Arming
05 = Arm with WinLoad Software
07 = Closing Delinquency (Partition 1 only)
99 = Any Sub-Group
15 = Disarm with User Code
01 to 48 = User Code Numbers 001 to 048
99 = Any User Code
16 = Disarm After Alarm w/ User Code
01 to 48 = User Code Numbers 001 to 048
99 = Any User Code
17 = Cancel Alarm with User Code
01 to 48 = User Code Numbers 001 to 048
99 = Any User Code
18 = Special Disarm
00 = Cancel Auto Arm (timed/no movement)
01 = Disarm with WinLoad Software
02 = Disarm after alarm with WinLoad Software
03 = Cancel Alarm with WinLoad Software
99 = Any Sub-Group
19 = Zone Bypassed on Arming
01 to 15 = Zones 1 to 15
99 = Any Zone
20 = Zone in Alarm
01 to 15 = Zones 1 to 15
99 = Any Zone
21 = Fire Alarm
01 to 05 = Zones 1 to 5 (on-board inputs)
99 = Any Zone
22 = Zone Alarm Restore
01 to 15 = Zones 1 to 15
99 = Any Zone
23 = Fire Alarm Restore
01 to 05 = Zones 1 to 5 (on-board inputs)
99 = Any Zone
24 = Special Alarm
00 = Emergency Panic
01 = Auxiliary Panic
02 = Fire Panic
03 = Recent Closing
04 = Auto Zone Shutdown
05 = Duress Alarm
06 = Keypad Lockout
99 = Any Sub-Group
25 = Auto Zone Shutdown
01 to 15 = Zones 1 to 15
99 = Any Zone
26 = Zone Tamper
01 to 15 = Zones 1 to 15
99 = Any Zone
27 = Zone Tamper Restore
01 to 15 = Zones 1 to 15
99 = Any Zone
Event Group # Sub-Group #
Spectra 1759MG - 11 - Programming Guide
28 = System Trouble
01 = AC Loss: only after Power Failure Delay has elapsed (Partition 1 only)
02 = Battery Failure (Partition 1 only)
03 = Auxiliary current overload (Partition 1 only)
04 = Bell current overload (Partition 1 only)
05 = Bell disconnected (Partition 1 only)
06 = Timer Loss (Partition 1 only)
07 = Fire Loop Trouble (Partition 1 only)
08 = Future Use
09 = Module Fault (Partition 1 only)
10 = Printer Fault (Partition 1 only)
11 = Fail to Communicate (Partition 1 only)
99 = Any Sub-Group (Partition 1 only)
29 = System Trouble Restore
00 = TLM restore (Partition 1 only)
01 = AC Loss restore (Partition 1 only)
02 = Battery Failure restore (Partition 1 only)
03 = Auxiliary current overload restore (Partition 1 only)
04 = Bell current overload restore (Partition 1 only)
05 = Bell disconnected restore (Partition 1 only)
06 = Timer Programmed (Partition 1 only)
07 = Fire Loop Trouble restore (Partition 1 only)
08 = Future Use
09 = Module Fault restore (Partition 1 only)
10 = Printer Fault restore (Partition 1 only)
11 = Fail to Communicate restore (Partition 1 only)
99 = Any Trouble Restore (Partition 1 only)
30 = Special Reporting
00 = System Power Up (Partition 1 only)
01 = Test Report (Partition 1 only)
02 = WinLoad Software Access (Partition 1 only)
03 = WinLoad Software Access finished (Partition 1 only)
04 = Installer enters programming mode (Partition 1 only)
05 = Installer exits programming mode (Partition 1 only)
99 = Any Sub-Group (Partition 1 only)
31 = Wireless Transmitter Supervision Loss
01 to 15 = Zones 1 to 15
99 = Any Zone
32 = Wireless Transmitter Supervision Loss Restore
01 to 15 = Zones 1 to 15
99 = Any Zone
33 = Arming with a Keyswitch
01 to 05 = Zones 1 to 5 (on-board inputs)
99 = Any Zone
34 = Disarming with a Keyswitch
01 to 05 = Zones 1 to 5 (on-board inputs)
99 = Any Zone
35 = Disarm after Alarm with a Keyswitch
01 to 05 = Zones 1 to 5 (on-board inputs)
99 = Any Zone
36 = Cancel Alarm with a Keyswitch
01 to 05 = Zones 1 to 5 (on-board inputs)
99 = Any Zone
37 = Wireless Transmitter Low Battery
01 to 15 = Zones 1 to 15
99 = Any Zone
38 = Wireless Transmitter Low Battery Restore
01 to 15 = Zones 1 to 15
99 = Any Zone
Event Group #
Sub-Group #
Partition #
80 = PGM follows Clock (APR3-PGM4 only)
HH = hour according to 24hr. clock
MM = minutes according to 24hr. clock
Event Group # Sub-Group #
Spectra 1759MG - 12 - Programming Guide
System Options
Bold = Default Setting
* Reassign Keypad Zone 2 and Reassign zones to expansion inputs change the zone numbering to increase the number of expansion inputs that can be displayed on 10-Zone LED Keypads. Refer to the Zone Recognition Table on page 6 and the Spectra 1759MG Reference & Installation Manual for details.
Section [126]: General Options
Option
OFF
ON
[1]
Confidential Mode
l Disabled l Enabled
[2]
To exit Confidential Mode l Enter Access Code l Press a Key
[3]
Confidential Mode timer l 2 minutes l 5 seconds
[4]
PGM1 normal state l Normally Open (N.O.) l Normally Closed (N.C.)
[5]
PGM2 normal state l Normally Open (N.O.) l Normally Closed (N.C.)
[6]
Global PGM normal state l Normally Open (N.O.) l Normally Closed (N.C.)
[7]
Reassign Keypad Zone 2* l Disabled l Enabled
[8]
Reassign zones to expansion inputs* l Disabled l Enabled
Section [127]: General Options
Option
OFF
ON
[1]
Partitioning l Disabled l Enabled
[2]
Access code length l 6-digits l 4-digits
[3]
Keypad audible trouble warning l Disabled l Enabled
[4]
Lock System Master Code l Disabled l Enabled
[5]
Battery charge current l 350mA l 700mA
[6]
User Code 048 is a Duress Code l Disabled l Enabled
[7]
Alarm relay follows l Bell Output l Global PGM
[8]
Future use l N/A l N/A
Section [128]: General Options
Option
OFF
ON
[1]
Panic 1: keys [1] & [3] l Disabled l Enabled
[2]
Panic 2: keys [4] & [6] l Disabled l Enabled
[3]
Panic 3: keys [7] & [9] l Disabled l Enabled
[4]
Panic 1: silent or audible l Silent l Audible
[5]
Panic 2: silent or audible l Silent l Audible
[6]
Panic 3: silent or fire l Silent l Fire
[7]
Keypad 1 tamper supervision l Disabled l Enabled
[8]
Keypad 2 tamper supervision l Disabled l Enabled
Section [129]: General Options
Option
OFF
ON
[1]
PGM2 output activation option l Steady l Pulse (flash)
[2]
PGM2 pulse once every 30 sec. if system armed l Disabled l Enabled
[3]
PGM2 pulse on Arm, twice on Disarm l Disabled l Enabled
[4]
ZX4 & ZX8 zone expansion module supervision l Disabled l Enabled
[5]
Future use l N/A l N/A
[6]
Wireless module low battery supervision l Disabled l Enabled
[7]
4-PGM Output Module supervision (APR3-PGM4) l Disabled l Enabled
[8]
Printer Module supervision (APR3-PRT1) l Disabled l Enabled
Spectra 1759MG - 13 - Programming Guide
Bold = Default Setting
* This option cannot be done using a keyswitch. Force arming is not supported by keyswitches.
Section [130]: Arming/Disarming Options
Option
OFF
ON
[1]
One-touch Regular Arming l Disabled l Enabled
[2]
One-touch Stay Arming l Disabled l Enabled
[3]
One-touch Force Arming l Disabled l Enabled
[4]
One-touch bypass programming l Disabled l Enabled
[5]
Restrict arming on battery failure l Disabled l Enabled
[6]
Restrict arming on Tamper failure l Disabled l Enabled
[7]
Bell Squawk on Arm/Disarm with keypad l Disabled l Enabled
[8]
Beep on exit delay l Disabled l Enabled
Section [131]: Arming/Disarming Options
Option
OFF
ON
[1]
Report Disarming l Always l Only after alarm
[2]
Regular Arming switches to Force Arming * l Disabled l Enabled
[3]
Bell Squawk on Arm/Disarm with remote control
(must be enabled for UL installations) l Disabled l Enabled
[4]
No exit delay when Arming with a remote control l Disabled l Enabled
[5]
No exit delay beeps and no Bell Squawk when Stay Arming l Disabled l Enabled
[6]
Restrict arming on wireless transmitter supervision loss l Disabled l Enabled
[7]
Generate supervision loss if detected on bypassed wireless zone l Yes l No
[8]
Future Use l N/A l N/A
Section [132]: Zone Options
Option
OFF
ON
[1]&[2] l see table l see table l see table l see table
[3]
Generate tamper if detected on bypassed zone l Yes l No
[4]
EOL (end-of-line) resistors l No EOL l Use EOL Resistors
[5]
Future use l N/A l N/A
[6]
Report zone restore l On Bell Cut-off l On Zone Closure
[7]&[8] l see table l see table l see table l see table
Tamper Recognition Options[1][2]OFFOFFDisabled (default)OFFONWhen disarmed: GENERATES TROUBLE ONLYWhen armed: Follows Zone Alarm Types ONOFFWhen disarmed: GENERATES SILENT ALARMWhen armed: Follows Zone Alarm TypesONONWhen disarmed: GENERATES AUDIBLE ALARMWhen armed: Follows Zone Alarm Types
Wireless Transmitter Supervision Options[7][8]OFFOFFDisabled (default)OFFONWhen disarmed: GENERATES TROUBLE ONLYWhen armed: Follows Zone Alarm Types ONOFFWhen disarmed: GENERATES SILENT ALARMWhen armed: Follows Zone Alarm TypesONONWhen disarmed: GENERATES AUDIBLE ALARMWhen armed: Follows Zone Alarm Types
Spectra 1759MG - 14 - Programming Guide
Bold = Default Setting
Section [133]: Partition 1 Options
Option
OFF
ON
[1]
Auto-arm on time l Disabled l Enabled
[2]
Auto-arm on no movement l Disabled l Enabled
[3]
Auto Arming = Regular or Stay l Regular Arming l Stay Arming
[4]
Switch to Stay Arming if no entry delay is opened l Disabled l Enabled
[5]
Stay Arming with Delay Partition 1 (Delay = [070]) l Disabled l Enabled
[6] to [8]
Future use l N/A l N/A
Section [134]: Partition 2 Options
Option
OFF
ON
[1]
Auto-arm on time l Disabled l Enabled
[2]
Auto-arm on no movement l Disabled l Enabled
[3]
Auto Arming = Regular or Stay l Regular Arming l Stay Arming
[4]
Switch to Stay Arming if no entry delay is opened l Disabled l Enabled
[5]
Stay Arming with Delay Partition 2 (Delay = [070]) l Disabled l Enabled
[6] to [8]
Future use l N/A l N/A
Section [135]: Dialer Options
Option
OFF
ON
[1] & [2] l see table l see table l see table l see table
[3]
Reporting (Dialer) l Disabled l Enabled
[4]
Dialing method l Pulse Dialing l Tone (DTMF) Dialing
[5]
Pulse ratio l 1:2 l 1:1.5
[6]
If armed, activate bell output on Com. Failure l Disabled l Enabled
[7] & [8]
Future use l N/A l N/A
Section [136]: Dialer Options
Option
OFF
ON
[1]
Call back WinLoad l Disabled l Enabled
[2]
Automatic event buffer transmission l Disabled l Enabled
[3]
Contact I.D. report codes l Programmable l All Codes (automatic)
[4]
Alternate dial l Disabled l Enabled
[5]
If no dial tone is present l Continue after 4 sec. l Hang-up after 16 sec.
[6] & [7] l see table l see table l see table l see table
[8]
Pager Format Transmission Options l Transmit report code after Pager delay l Transmit report code immediately
Telephone Line Monitoring (TLM) Options[1][2]OFFOFFTLM Disabled (default)OFFONTLM generates a trouble if armedONOFFTLM generates an audible alarm if armedONONSilent alarms become audible
Pager Reporting Format Dialer Options[6][7]OFFOFF1 call to pager or cellular telephone (default)OFFON2 calls to pager or cellular telephoneONOFF3 calls to pager or cellular telephoneONON4 calls to pager or cellular telephone
Spectra 1759MG - 15 - Programming Guide
Bold = Default Setting
Communication Settings
Section [137]: Event Call Direction
Option
OFF
ON
[1]
Call Telephone #1 for Arming/Disarming Report Codes l Disabled l Enabled
[2]
Call Telephone #2 for Arming/Disarming Report Codes l Disabled l Enabled
[3]
Call Telephone #1 for Alarm/Restore Report Codes l Disabled l Enabled
[4]
Call Telephone #2 for Alarm/Restore Report Codes l Disabled l Enabled
[5]
Call Telephone #1 for Tamper/Restore Report Codes l Disabled l Enabled
[6]
Call Telephone #2 for Tamper/Restore Report Codes l Disabled l Enabled
[7] & [8]
Future use l N/A l N/A
Section [138]: Event Call Direction
Option
OFF
ON
[1]
Call Telephone #1 for Trouble/Restore Report Codes l Disabled l Enabled
[2]
Call Telephone #2 for Trouble/Restore Report Codes l Disabled l Enabled
[3]
Call Telephone #1 for Special Report Codes l Disabled l Enabled
[4]
Call Telephone #2 for Special Report Codes l Disabled l Enabled
[5] to [8]
Future use l N/A l N/A
Section #
[140]
___ / ___
TEL1 TEL2
REPORTING FORMATS
1
= ADEMCO SLOW (1400HZ, 1900HZ, 10BPS)
2
= SILENT KNIGHT FAST (1400HZ, 1900HZ, 20BPS)
3
= SESCOA (2300HZ, 1800HZ, 20BPS)
4
= ADEMCO EXPRESS (DTMF 4+2)
5 = ADEMCO CONTACT ID (DEFAULT) see option [3] in section [136] on page 14
6
= PAGER FORMAT
If Hexadecimals (0 to FF) are used to program the report codes, verify that the pager also supports Hexadecimals. If the pager does not support Hexadecimals, use only the digits 0 to 9.
[141]
___/___/___/___
PANEL IDENTIFIER (WINLOAD SOFTWARE)
[142]
___/___/___/___
PC PASSWORD (WINLOAD SOFTWARE)
[143]
___/___/___/___
PARTITION ACCOUNT NUMBER 1 (For less than 4 digits, use the [FORCE] key to enter blanks.)
[144]
___/___/___/___
PARTITION ACCOUNT NUMBER 2 (For less than 4 digits, use the [FORCE] key to enter blanks.)
[150]
__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
PC TELEPHONE NUMBER FOR WINLOAD SOFTWARE (32-digits, if less than 32 press [ENTER] to accept)
[151]
__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
CENTRAL STATION TELEPHONE OR PAGER NUMBER 1 (32-digits, if less than 32 press [ENTER] to accept)
[152]
__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
CENTRAL STATION TELEPHONE OR PAGER NUMBER 2 (32-digits, if less than 32 press [ENTER] to accept)
[153]
__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
BACK UP TELEPHONE NUMBER (32-digits, if less than 32 press [ENTER] to accept)
Special Keys for Telephone Numbers
[STAY] = *
[MEM] = Switch from pulse to tone dialing or vice versa
[FORCE] = Delete current digit
[BYP] = #
[TBL] or [TRBL] = 4-second pause
[PG] or [FNC1] = Inserts Blank Space
Spectra 1759MG - 16 - Programming Guide
Report Codes
Ademco Slow, Silent Knight, SESCOA, Ademco Express and Pager Formats: Enter the desired 1- or 2-digit hex-value (0-F or 00-FF). Ademco “Programmable” Format: Enter the desired 2-digit hex values from the “Ademco Report Code List - Programmable” (see Appendix A on page 30). Also Note that entering FF will set the report code to the default Ademco Report Code. Ademco “All Codes” Format: The control panel automatically generates report codes from the “Ademco Report Code List - All Codes” (see Appendix B on page 31).
Arming Report Codes
[160]
___/___Access Code 01
___/___Access Code 02
___/___Access Code 03
___/___Access Code 04
[165]
___/___Access Code 21
___/___Access Code 22
___/___Access Code 23
___/___Access Code 24
[170]
___/___Access Code 41
___/___Access Code 42
___/___Access Code 43
___/___Access Code 44
[161]
___/___Access Code 05
___/___Access Code 06
___/___Access Code 07
___/___Access Code 08
[166]
___/___Access Code 25
___/___Access Code 26
___/___Access Code 27
___/___Access Code 28
[171]
___/___Access Code 45
___/___Access Code 46
___/___Access Code 47
___/___Access Code 48
[162]
___/___Access Code 09
___/___Access Code 10
___/___Access Code 11
___/___Access Code 12
[167]
___/___Access Code 29
___/___Access Code 30
___/___Access Code 31
___/___Access Code 32
Special Arming Codes
[163]
___/___Access Code 13
___/___Access Code 14
___/___Access Code 15
___/___Access Code 16
[168]
___/___Access Code 33
___/___Access Code 34
___/___Access Code 35
___/___Access Code 36
[172]
___/___Auto-Arming
___/___Late to Close
___/___No Movement
___/___Partial Arming
[164]
___/___Access Code 17
___/___Access Code 18
___/___Access Code 19
___/___Access Code 20
[169]
___/___Access Code 37
___/___Access Code 38
___/___Access Code 39
___/___Access Code 40
[173]
___/___Quick Arming
___/___Arming via PC
___/___Keyswitch Arming
___/___Closing Delinquency
Disarming Report Codes
[174]
___/___Access Code 01
___/___Access Code 02
___/___Access Code 03
___/___Access Code 04
[179]
___/___Access Code 21
___/___Access Code 22
___/___Access Code 23
___/___Access Code 24
[184]
___/___Access Code 41
___/___Access Code 42
___/___Access Code 43
___/___Access Code 44
[175]
___/___Access Code 05
___/___Access Code 06
___/___Access Code 07
___/___Access Code 08
[180]
___/___Access Code 25
___/___Access Code 26
___/___Access Code 27
___/___Access Code 28
[185]
___/___Access Code 45
___/___Access Code 46
___/___Access Code 47
___/___Access Code 48
[176]
___/___Access Code 09
___/___Access Code 10
___/___Access Code 11
___/___Access Code 12
[181]
___/___Access Code 29
___/___Access Code 30
___/___Access Code 31
___/___Access Code 32
Special Disarming Codes
[177]
___/___Access Code 13
___/___Access Code 14
___/___Access Code 15
___/___Access Code 16
[182]
___/___Access Code 33
___/___Access Code 34
___/___Access Code 35
___/___Access Code 36
[186]
___/___Cancel Auto-Arm
___/___Disarming via PC
___/___Keyswitch Disarm
___/___N/A
[178]
___/___Access Code 17
___/___Access Code 18
___/___Access Code 19
___/___Access Code 20
[183]
___/___Access Code 37
___/___Access Code 38
___/___Access Code 39
___/___Access Code 40
Spectra 1759MG - 17 - Programming Guide
Alarm Report Codes
Alarm
Restore
Special
[187]
___/___Zone 01
___/___Zone 02
___/___Zone 03
___/___Zone 04
[191]
___/___Zone 01
___/___Zone 02
___/___Zone 03
___/___Zone 04
[195]
___/___Emergency Panic
___/___Auxiliary Panic
___/___Fire Panic
___/___Recent Closing
[188]
___/___Zone 05
___/___Zone 06
___/___Zone 07
___/___Zone 08
[192]
___/___Zone 05
___/___Zone 06
___/___Zone 07
___/___Zone 08
[196]
___/___Zone Shutdown
___/___Duress
___/___Keypad Lockout
___/___N/A
[189]
___/___Zone 09
___/___Zone 10
___/___Zone 11
___/___Zone 12
[193]
___/___Zone 09
___/___Zone 10
___/___Zone 11
___/___Zone 12
[190]
___/___Zone 13
___/___Zone 14
___/___Zone 15
___/___N/A
[194]
___/___Zone 13
___/___Zone 14
___/___Zone 15
___/___N/A
Tamper Report Codes
[197]
Trouble
___/___Zone 01
___/___Zone 02
___/___Zone 03
___/___Zone 04
[200]
___/___Zone 13
___/___Zone 14
___/___Zone 15
___/___N/A
[203]
___/___Zone 09
___/___Zone 10
___/___Zone 11
___/___Zone 12
[198]
___/___Zone 05
___/___Zone 06
___/___Zone 07
___/___Zone 08
[201]
Restore
___/___Zone 01
___/___Zone 02
___/___Zone 03
___/___Zone 04
[204]
___/___Zone 13
___/___Zone 14
___/___Zone 15
___/___N/A
[199]
___/___Zone 09
___/___Zone 10
___/___Zone 11
___/___Zone 12
[202]
___/___Zone 05
___/___Zone 06
___/___Zone 07
___/___Zone 08
System Trouble Report Codes
System Trouble
Restore
Special
[205]
___/___N/A
___/___AC Failure
___/___Battery Failure
___/___Auxiliary Supply
[208]
___/___TLM
___/___AC Failure
___/___Battery Failure
___/___Auxiliary Supply
[211]
___/___Cold Start (Shutdown)
___/___Test Report
___/___N/A
___/___PC Exit
[206]
___/___Bell Output Overload
___/___Bell Output Disconnect
___/___Timer Loss
___/___Fire Loop Trouble
[209]
___/___Bell Output Overload
___/___Bell Output Disconnect
___/___Timer Loss
___/___Fire Loop Trouble
[212]
___/___Installer In
___/___Installer Out
___/___N/A
___/___N/A
[207]
___/___Wireless Low Battery
___/___Module Fault
___/___Printer Fault
___/___Fail to Communicate
[210]
___/___Wireless Low Battery
___/___Module Fault
___/___Printer Fault
___/___Fail to Communicate
[213]
___/___TX Supervision Loss
___/___TX Supervision Restore
___/___N/A
___/___N/A
Spectra 1759MG - 18 - Programming Guide
System Settings
User Code Options
System Master Code arms or disarm partitions using any arming method and can create, modify or delete any User Access Code. Only the System Master Code can modify or delete User Access Codes assigned to both partitions.
Master Code 1 is permanently assigned to partition 1 and can be used to create, modify or delete User Access Codes that are assigned to partition 1.
Master Code 2 is permanently assigned to partition 2 (except when partitioning is disabled, Master Code 2 will be assigned to partition 1) and can be used to create, modify or delete User Access Codes that are assigned to the same partition.
Section #
Description
[280]
___/___:___/___
SYSTEM REAL TIME CLOCK (HH:MM)
[281]
___/___/___/___/___/___
INSTALLER CODE, DEFAULT: 0000 / 000000
[282]
___/___/___
INSTALLER CODE LOCK, DEFAULT: 000 (147 TO LOCK, 000 TO UNLOCK)
[301]
___/___/___/___/___/___
SYSTEM MASTER CODE, DEFAULT: 1234 / 123456
Default for all user codes is options [1], [3] and [4] ON.
ON = Option Enabled
OFF = Option Disabled
[1] ON = Partition 1 Access
[2] ON = Partition 2 Access
[3] ON = Bypass Programming
[4] ON = Stay Arming
[5] ON = Force Arming
[6] ON = Arm Only
[7] ON = PGM Activation Only
[8] ON = Future Use
Section #
User Code Options (ON/OFF)
Section
User Code Options (ON/OFF)
[302]
Master Code 1
12345678
[325]
User Code 025
12345678
[303]
Master Code 2
12345678
[326]
User Code 026
12345678
[304]
User Code 004
12345678
[327]
User Code 027
12345678
[305]
User Code 005
12345678
[328]
User Code 028
12345678
[306]
User Code 006
12345678
[329]
User Code 029
12345678
[307]
User Code 007
12345678
[330]
User Code 030
12345678
[308]
User Code 008
12345678
[331]
User Code 031
12345678
[309]
User Code 009
12345678
[332]
User Code 032
12345678
[310]
User Code 010
12345678
[333]
User Code 033
12345678
[311]
User Code 011
12345678
[334]
User Code 034
12345678
[312]
User Code 012
12345678
[335]
User Code 035
12345678
[313]
User Code 013
12345678
[336]
User Code 036
12345678
[314]
User Code 014
12345678
[337]
User Code 037
12345678
[315]
User Code 015
12345678
[338]
User Code 038
12345678
[316]
User Code 016
12345678
[339]
User Code 039
12345678
[317]
User Code 017
12345678
[340]
User Code 040
12345678
[318]
User Code 018
12345678
[341]
User Code 041
12345678
[319]
User Code 019
12345678
[342]
User Code 042
12345678
[320]
User Code 020
12345678
[343]
User Code 043
12345678
[321]
User Code 021
12345678
[344]
User Code 044
12345678
[322]
User Code 022
12345678
[345]
User Code 045
12345678
[323]
User Code 023
12345678
[346]
User Code 046
12345678
[324]
User Code 024
12345678
[347]
User Code 047
12345678
[348]
User Code 048
12345678
Spectra 1759MG - 19 - Programming Guide
Reprogram All Modules
Paradox Memory Key (PMC-3)
Download to DESTINATION Control Panel
1)Remove AC and battery power from the control panel.
2)Insert the Memory Key onto the serial connector labelled KEY on the Spectra control panel to which you wish to download the contents of the memory key to.
3)Re-apply AC and battery power.
4)Enter installer programming mode, enter section [900], then press [ENTER] to acknowledge.
5)When the keypad emits a “confirmation beep”, remove the Memory Key.
6)Enter section [750] to reprogram the modules with the information downloaded from the Paradox Memory Key.
Copy to Memory Key from SOURCE Control Panel
1)Remove AC and battery power from the control panel.
2)Insert Memory Key onto the serial connector labelled KEY on the Spectra control panel that you want to copy. Make sure the write protect jumper of the Memory Key is on.
3)Re-apply AC and battery power.
4)Enter installer programming mode, enter section [902], then press [ENTER] to acknowledge.
5)When the keypad emits a Confirmation Beep, remove the Memory Key. Remove the Memory Key’s jumper if you do not wish to accidentally overwrite its contents.
[750]
After removing an expansion module from the communication bus, the control panel keeps the module’s programmed sections in memory. Therefore, if you add or replace a module you can re-program the module with the settings saved in the control panel. To do so, enter section [750] and press [ENTER]. The keypads will beep twice every second until the procedure is completed.
[900]
DOWNLOAD FROM PARADOX MEMORY KEY TO DESTINATION CONTROL PANEL.
[902]
COPY TO MEMORY KEY FROM SOURCE CONTROL PANEL.
Jumper ON = Read from and/or write to memory keyParadox Memory Key PMC-3Jumper OFF = Write protected (read from memory key only)Insert Paradox Memory Key onto the ‘MEMORY KEY’ connector.Partial view of Spectra 1759MG control panel
Spectra 1759MG - 20 - Programming Guide
4-PGM Output Modules V2.0
Due to the APR3-PGM4’s Auto-recognition feature, it can be used with either the Spectra (V2.0 or higher), DGP-848 or
DGP-NE96 control panel. When connected to the bus, the APR3-PGM4 automatically detects which control panel it is connected to and adjusts its internal communication parameters to function accordingly. Only one APR3-PGM4 can be connected to each Spectra control panel.
Modules with the APR- prefix are compatible with Spectra (versions 2.0 and higher) and DGP-848. Modules with the APR3- prefix are compatible with Spectra (versions 2.0 and higher), DGP-848 and DGP-NE96.
Bold = Default Setting
PGM Programming
Each PGM Deactivation event can be used as another activation event if their respective PGM timer (see sections [501] to [504]) is programmed with a value other than 000. The APR3-PGM4 uses the same PGM events as the Spectra control panel, please refer to Programmable Outputs on page 9.
Section #Decimal Value (000-255)DescriptionDefault Value
[501] ___/___/___(000 = follow deactivation event)PGM1 TIMER5 sec.
[502] ___/___/___(000 = follow deactivation event)PGM2 TIMER5 sec.
[503] ___/___/___(000 = follow deactivation event)PGM3 TIMER5 sec.
[504] ___/___/___(000 = follow deactivation event)PGM4 TIMER5 sec.
Section #Event Group #Sub-Group #Partition #
[505] PGM1 Activation Event___/______/______/___
[506] PGM1 Deactivation Event___/______/______/___
[507] PGM2 Activation Event___/______/______/___
[508] PGM2 Deactivation Event___/______/______/___
[509] PGM3 Activation Event___/______/______/___
[510] PGM3 Deactivation Event___/______/______/___
[511] PGM4 Activation Event___/______/______/___
[512] PGM4 Deactivation Event___/______/______/___
Section [500]: General Options
Option
OFF
ON
[1]
PGM1 Time Base Selection l Seconds l Minutes
[2]
PGM2 Time Base Selection l Seconds l Minutes
[3]
PGM3 Time Base Selection l Seconds l Minutes
[4]
PGM4 Time Base Selection l Seconds l Minutes
[5] to [8]
Future use l N/A l N/A
Spectra 1759MG - 21 - Programming Guide
Printer Module V2.0
Due to the APR3-PRT1’s Auto-recognition feature, it can be used with either the Spectra (V2.0 or higher), DGP-848 or
DGP-NE96 control panel. When connected to the bus, the APR3-PRT1 automatically detects which control panel it is connected to and adjusts its internal communication parameters to function accordingly. Only one APR3-PRT1 can be connected to each Spectra control panel.
Modules with the APR- prefix are compatible with Spectra (versions 2.0 and higher) and DGP-848. Modules with the APR3- prefix are compatible with Spectra (versions 2.0 and higher), DGP-848 and DGP-NE96.
Bold = Default Setting
Section [550]: General Options
Option
OFF
ON
[1]
Assigned to Partition 1 l Disabled l Enabled
[2]
Assigned to Partition 2 l Disabled l Enabled
[3]
PGM normal state l Normally Open (N.O.) l Normally Closed (N.C.)
[4]
Print Arming and disarming events l Disabled l Automatically
[5]
Print Alarm and Alarm Restore events l Disabled l Automatically
[6]
Print Tamper and Tamper Restore events l Disabled l Automatically
[7]
Print Trouble and Trouble Restore events l Disabled l Automatically
[8]
Print Special events l Disabled l Automatically
Section [551]: Automatic Zone Status Printing
Option
OFF
ON
[1]
Print status of Zone 1 l Disabled l Automatically
[2]
Print status of Zone 2 l Disabled l Automatically
[3]
Print status of Zone 3 l Disabled l Automatically
[4]
Print status of Zone 4 l Disabled l Automatically
[5]
Print status of Zone 5 l Disabled l Automatically
[6]
Print status of Zone 6 l Disabled l Automatically
[7]
Print status of Zone 7 l Disabled l Automatically
[8]
Print status of Zone 8 l Disabled l Automatically
Section [552]: Automatic Zone Status Printing
Option
OFF
ON
[1]
Print status of Zone 9 l Disabled l Automatically
[2]
Print status of Zone 10 l Disabled l Automatically
[3]
Print status of Zone 11 l Disabled l Automatically
[4]
Print status of Zone 12 l Disabled l Automatically
[5]
Print status of Zone 13 l Disabled l Automatically
[6]
Print status of Zone 14 l Disabled l Automatically
[7]
Print status of Zone 15 l Disabled l Automatically
[8]
N/A l N/A l N/A
Spectra 1759MG - 22 - Programming Guide
Bold = Default Setting
PGM Programming
The PGM Deactivation event can be used as another activation event if the PGM Timer (section [554]) is programmed with a value other than 000. The APR3-PRT1 module uses the same PGM events as the Spectra control panel, please refer to Programmable Outputs on page 9.
Section # Decimal Value (000-255)DescriptionDefault Value
[554] ___/___/___seconds (000 = follow deactivation event)PGM1 TIMER5s
Section #Event Group #Sub-Group #Partition #
[555] PGM1 Activation Event___/______/______/___
[556] PGM1 Deactivation Event___/______/______/___
Clock Programming
For example, to enter the date March 26, 2004 you would enter 2004 (year), 03 (month), and 26 (day).
Section #Value
[557]Year ___/___/___/___ Month ___/___ Day ___/___
Section [553]: Serial and Parallel Port Setup Options
Option
OFF
ON
[1]
Serial port l Disabled l Enabled
[2]&[3] l see table l see table l see table l see table
[4]
Parallel port l Disabled l Enabled
[5]
Off-line status ignored (parallel port only) l Disabled l Enabled
[6]
Paper empty status ignored (parallel port only) l Disabled l Enabled
[7]
Printer fault status ignored (parallel port only) l Disabled l Enabled
[8]
Printer busy status ignored (parallel port only) l Disabled l Enabled
Baud Rate Settings[2][3]APR-PRT1APR3-PRT1OFFOFF1200 baud (default)2400 baud (default)ONOFF2400 baud9600 baudOFFON9600 baud19200 baudONON19200 baud57600 baud
Spectra 1759MG - 23 - Programming Guide
Voice-assisted Arm/Disarm Bus Module V2.0
Due to InTouch’s Auto-recognition feature, it can be used with either the Spectra (V2.0 or higher), DGP-848 or DGP-NE96 control panels. When connected to the bus, InTouch automatically detects which control panel it is connected to and adjusts its internal communication parameters to function accordingly. Only one InTouch can be connected to each Spectra control panel.
APR3-ADM2 can also be programmed using the WinLoad Software. Refer to the WinLoad Online Help for more information.
Modules with the APR- prefix are compatible with Spectra (versions 2.0 and higher) and DGP-848. Modules with the APR3- prefix are compatible with Spectra (versions 2.0 and higher), DGP-848 and DGP-NE96.
Section #Decimal Value (000-255)DescriptionDefault Value
[575] ___/___/___rings (000 = disabled)NUMBER OF RINGS8 rings
[576] ___/___/___seconds (010-255, 000 = disabled)ANSWERING MACHINE OVERRIDE000
[577] ___/___/___seconds/minutes (000 = disabled)PGM TIMER005
Bold = Default Setting
To reset the standalone code of the APR3-ADM2, you have to perform a hardware reset of the Spectra control panel.
Section [578]: General Options
Option
OFF
ON
[1]
Stand-alone Code length l 6-digits l 4-digits
[2]
Partitioned system l Disabled l Enabled
[3]
PGM output l Disabled l Enabled
[4]
PGM time in l Seconds l Minutes
[5] to [8]
Future use l N/A l N/A
Spectra 1759MG - 24 - Programming Guide
Wireless Features
Do not cut, bend or alter 1759MG’s antennae and ensure that electrical wires do not cross over the antennae, as this may affect signal reception.
Zone Assignment
The serial number can be located on the inside of the transmitter or you can use the Serial Number Display feature (see page 24). Also, refer to Zone Recognition Table on page 6.
Section # Serial #
[601] ___/___/___/___/___/___= EXPANSION INPUT 1
[602] ___/___/___/___/___/___= EXPANSION INPUT 2
[603] ___/___/___/___/___/___= EXPANSION INPUT 3
[604] ___/___/___/___/___/___= EXPANSION INPUT 4
[605] ___/___/___/___/___/___= EXPANSION INPUT 5
[606] ___/___/___/___/___/___= EXPANSION INPUT 6
[607] ___/___/___/___/___/___= EXPANSION INPUT 7
[608] ___/___/___/___/___/___= EXPANSION INPUT 8
Bold = Default Setting
Serial Number Display
Section #Description
[630]Press the anti-tamper switch of the Magellan Wireless Transmitter. The keypad will emit a confirmation beep. On LED keypads, press the [ENTER] key to view the digits one at a time. On LCD keypads, the first 3 digits of the serial number will appear. Press the [ENTER] key 3 times to view the next 3 digits. Continue activating the desired transmitters or press [CLEAR] to exit.
Signal Strength Display
Section #Description
After entering the desired section, activate the Magellan Wireless Transmitter by opening/closing the zone or by pressing the anti-tamper switch. Always ignore the first reading as it won’t be accurate. An average reading of 3 or higher is acceptable.
[631]Display Signal Strength of Expansion Input 1 - Section [601]
[632]Display Signal Strength of Expansion Input 2 - Section [602]
[633]Display Signal Strength of Expansion Input 3 - Section [603]
[634]Display Signal Strength of Expansion Input 4 - Section [604]
[635]Display Signal Strength of Expansion Input 5 - Section [605]
[636]Display Signal Strength of Expansion Input 6 - Section [606]
[637]Display Signal Strength of Expansion Input 7 - Section [607]
[638]Display Signal Strength of Expansion Input 8 - Section [608]
Section [610]: General Options
Option
OFF
ON
[1]
Wireless transmitter check-in supervision l Disabled l Enabled
[2]
Check-in supervision interval l 24h l 80min
[3] to [7]
Future use l N/A l N/A
[8]
Tamper Supervision l Disabled l Enabled
Spectra 1759MG - 25 - Programming Guide
Remote Control User Assignment
Section #Decimal ValueDescriptionDefault Value
[701]___/___/___(001-048 = user #)remote control #1 - section [731]*000
[702]___/___/___(001-048 = user #)remote control #2 - section [732]*000
[703]___/___/___(001-048 = user #)remote control #3 - section [733]*000
[704]___/___/___(001-048 = user #)remote control #4 - section [734]*000
[705]___/___/___(001-048 = user #)remote control #5 - section [735]*000
[706]___/___/___(001-048 = user #)remote control #6 - section [736]*000
[707]___/___/___(001-048 = user #)remote control #7 - section [737]*000
[708]___/___/___(001-048 = user #)remote control #8 - section [738]*000
* refer to Remote Control Assignment on page 26.
Button Options
Please note that the User Code assigned to the remote control (sections [701] to [708]) must have the same User Options and Button Options enabled. For example, if you enable the Force Arming button option you must enable the appropriate Force Arming user option. Also, if you enable any of the Panic button options, you must enable the Panic options in the control panel.
Remote Control Button Programming
RC#
Section
RC Buttons
Default: ( 1 5 0 0 0 0 0 0 )
1
[711]
_____/_____/_____/_____/______/_____/_____/______
2
[712]
_____/_____/_____/_____/______/_____/_____/______
3
[713]
_____/_____/_____/_____/______/_____/_____/______
4
[714]
_____/_____/_____/_____/______/_____/_____/______
5
[715]
_____/_____/_____/_____/______/_____/_____/______
6
[716]
_____/_____/_____/_____/______/_____/_____/______
7
[717]
_____/_____/_____/_____/______/_____/_____/______
8
[718]
_____/_____/_____/_____/______/_____/_____/______
Button Options TableEmpty Slot [FORCE] - Button disabled1 - Regular arming2 - Stay arming3 - Instant arming4 - Force arming5 - Disarm6 - Disarm when no alarm7 - Regular arm and disarm8 - Panic 19 - Panic 2A - Panic 3B - PGM Activation (Event Group #7, see PGM Programming)C - PGM Activation (Event Group #8, see PGM Programming)D - PGM Activation (Event Group #9, see PGM Programming)MG-REM1++++++++++++++++++++++++++++++++
= These button combinations are not available with the MG-REM1or MG-RAC1 remote controls and cannot be programmed.
Spectra 1759MG - 26 - Programming Guide
Remote Control Assignment
Enter the appropriate section and press any button on the remote control twice to assign the remote control. If you hear a rejection beep, an error has occurred or the remote control has already been assigned. To delete a remote control, enter the desired section and then press the [FORCE] button.
Section #
[731]
REMOTE CONTROL #1
[732]
REMOTE CONTROL #2
[733]
REMOTE CONTROL #3
[734]
REMOTE CONTROL #4
[735]
REMOTE CONTROL #5
[736]
REMOTE CONTROL #6
[737]
REMOTE CONTROL #7
[
738]
REMOTE CONTROL #8
Spectra 1759MG - 27 - Programming Guide
Zone Expansion Bus Modules
Only one SPC/APR3-ZX4 or one SPC/APR3-ZX8 can be connected to each Spectra control panel. The following sections are for SPC-ZX4 version 1.0, APR3-ZX4 version 1.0, SPC-ZX8 version 1.0 and APR3-ZX8 version 2.0.
Modules with the APR- prefix are compatible with Spectra (versions 2.0 and higher) and DGP-848. Modules with the APR3- prefix are compatible with Spectra (versions 2.0 and higher), DGP-848 and DGP-NE96.
Bold = Default Setting
PGM Programming (SPC-ZX8 and APR3-ZX8 Only)
The PGM will only activate or deactivate 100mS after the selected event occurs. The PGM Deactivation event can be used as another activation event if the PGM Timer (section [655]) is programmed with a value other than 000. The system will ignore the PGM if it has been programmed to follow the Global PGM (option [3] in section [650]). Only PGM events from the table below can be used.
Section #Decimal Value (000-255)DescriptionDefault Value
[655] ___/___/___ seconds (000 = follow deactivation event)PGM1 TIMER 5 sec.
Section #Event Group #Sub-Group #Partition #
[656] PGM1 Activation Event___/______/______/___
[657] PGM1 Deactivation Event___/______/______/___
Section [650]: Options
Option
OFF
ON
[1]
EOL (end-of-line) resistors for hardwire modules l No EOL l Use EOL Resistors
[2]
Zone Expansion Module tamper recognition l Disabled l Z1 becomes tamper input
[3]
PGM1 on SPC/APR3-ZX8 follows Global PGM programmed in sections [124] & [125] l Disabled l Enabled
[4] to [8]
Future Use l N/A l N/A
Section [651]: Zone Assignment
Option
See Zone Recognition Table on page 6.
OFF
ON
[1]
Input Z1 =Expansion Input 1 l Disabled l Enabled
[2]
Input Z2 =Expansion Input 2 l Disabled l Enabled
[3]
Input Z3 =Expansion Input 3 l Disabled l Enabled
[4]
Input Z4 =Expansion Input 4 l Disabled l Enabled
[5]
Input Z5 (SPC/APR3-ZX8 only) =Expansion Input 5 l Disabled l Enabled
[6]
Input Z6 (SPC/APR3-ZX8 only) =Expansion Input 6 l Disabled l Enabled
[7]
Input Z7 (SPC/APR3-ZX8 only)=Expansion Input 7 l Disabled l Enabled
[8]
Input Z8 (SPC/APR3-ZX8 only)=Expansion Input 8 l Disabled l Enabled
Event Group #
Sub-Group #
Partition #
For SPC-ZX8:
60 = Hardwire Zone Opened
61 = Hardwire Zone Closed
62 = Hardwire Tamper Opened
63 = Hardwire Tamper Closed
For APR3-ZX8:
60 = Hardwire Zone/Hardwire Tamper Opened
61 = Hardwire Zone/Hardwire Tamper Closed
01 = Expansion Input 1 - Section [651] - [1]
02 = Expansion Input 2 - Section [651] - [2]
03 = Expansion Input 3 - Section [651] - [3]
04 = Expansion Input 4 - Section [651] - [4]
05 = Expansion Input 5 - Section [651] - [5]
06 = Expansion Input 6 - Section [651] - [6]
07 = Expansion Input 7 - Section [651] - [7]
08 = Expansion Input 8 - Section [651] - [8]
99 = Any zone expansion bus module input
Not used; enter 00
Spectra 1759MG - 28 - Programming Guide
User Operation
Partitioning
The Spectra system is equipped with a partitioning feature which can divide the alarm system into two distinct areas identified as Partition 1 and Partition 2. Partitioning can be used in installations where shared security systems are more practical, such as an office/warehouse building. If the system is not partitioned, all User Codes and features will be recognized as belonging to Partition 1.
Programming Access Codes
User Access Codes are personal identification numbers that allow users to enter certain programming modes, arm or disarm the alarm system as well as activate or deactivate PGMs. Spectra security systems support the following:
System Master Code can arm or disarm any partition using any arming method and can create, modify or delete any User Access Code. Only the System Master Code can modify or delete User Access Codes assigned to both partitions.
Master Code 1 is permanently assigned to partition 1 and can be used to create, modify or delete User Access Codes that are assigned to partition 1.
Master Code 2 is permanently assigned to partition 2 (except when partitioning is disabled, Master Code 2 will be assigned to partition 1) and can be used to create, modify or delete User Access Codes that are assigned to the same partition.
45 User Access Codes (including 1 Duress code)
How does a partitioned system work?
•Users can only arm or disarm their assigned partitions.
•Only zones assigned to Partition 1 will arm or disarm when Partition 1 is armed or disarmed.
•Only zones assigned to Partition 2 will arm or disarm when Partition 2 is armed or disarmed.
•Zones assigned to both partitions will arm when both partitions are armed and will disarm when at least one disarms.
•Some of the system’s features can be programmed separately for each partition.
How Do I Program Access Codes?
1)Press [ENTER]
2)Key in the [SYSTEM MASTER CODE] or [MASTER CODE]
3)Key in 3-digit [SECTION] (see User Code Table)
4)Key in new 4- or 6-digit [ACCESS CODE]
[ENTER] flashes. Return to step 3
How Do I Delete Access Codes?
1)Repeat steps 1 to 3 (see above)
2)Press the [FORCE] key once for each digit in the access code (4 or 6 times) until the keypad emits a Confirmation Beep.
User Code Table
Section
User Codes
[001]
User Code 001 = System Master Code
[002]
User Code 002 = Master Code 1
[003]
User Code 003 = Master Code 2
[004] TO [047]
User Code 004 to User Code 047
[048]
User Code 048 or Duress Code
Spectra 1759MG - 29 - Programming Guide
Programming Chime Zones
This feature allows users to program which zones will be Chime Enabled. A Chime Enabled zone will cause the keypad to emit a rapid intermittent beep tone (BEEP-BEEP-BEEP-BEEP) advising the user every time it is opened. Each keypad must be Chime Programmed separately. Keypad chimes must be re-programmed if the system suffers a total power loss (16-zone LED and LCD Keypads only).
10-Zone LED Keypad
Press and hold any key from [1] to [10] for 3 seconds to activate or deactivate Chiming for zones 1 to 10. For example, press and hold the [1] key to enable chiming on zone 1. If, after pressing and holding a key, the keypad emits a confirmation beep, this means the chime feature has been enabled for that zone. If the keypad emits a Rejection Beep, this means the Chime feature has been disabled for the corresponding zone.
16-Zone LED Keypad
Press and hold the [9] key. Enter the 2-digit (01 to 16) zone number(s). When the corresponding LED is on, the zone is chimed. When the corresponding LED is off, the zone is unchimed. When the desired zones are chimed, press [ENTER].
LCD Keypad
Press and hold the [9] key. Enter the 2-digit (01 to 16) zone number(s) or use the arrow keys to scroll through the zones. When the appropriate zone is displayed, press the [FNC1] key. When the desired zones are chimed, press [ENTER].
Keypad Muting
Press and hold the [CLEAR] key for 3 seconds to enable or disable keypad muting. When muted, the keypad will only beep when a key is pressed or when the keypad emits a Rejection or Confirmation Beep. All other beep functions are disabled.
Keypad Backlight (1686H and 1686V Only)
The illumination level behind the keys can be modified to suit the user’s needs. There are four backlight levels. The [MEM] key is used to set the desired level. Each consecutive push of the [MEM] key will increase the backlight level until the maximum level is reached. After reaching the maximum level, the backlight level will return to the lowest level and the whole process is repeated. To change the backlight level:
Installer Function Keys
Installer Test Mode
[ENTER] + [INSTALLER CODE] + [TBL] or [TRBL]
The Installer Test Mode allows you to perform walk tests where the bell/siren will squawk once to indicate an open zone and twice to indicate a closed zone. To enter this mode, press [ENTER] + [INSTALLER CODE] + [TBL] or [TRBL]. The keypad will emit a Confirmation Beep. To disable this mode, press the [TBL] or [TRBL] key again. The keypad will emit a Rejection Beep.
Test Report
[ENTER] + [INSTALLER/MASTER CODE] + [MEM]
Sends the Test Report report code programmed in section [211] to the central station.
Call WinLoad Software
[ENTER] + [INSTALLER/MASTER CODE] + [BYP]
This feature is used to establish communication between the control panel and a computer using the WinLoad Software. After entering this mode, the control panel will dial the telephone number programmed in section [150].
Cancel Communication
[ENTER] + [INSTALLER/MASTER CODE] + [STAY]
Cancels all communication until the next reportable event. If the Master Code was used, only communication with WinLoad would be cancelled.
Answer WinLoad Software
[ENTER] + [INSTALLER/MASTER CODE] + [FORCE]
Forces the control panel to pick-up an incoming telephone call.
How do I Modify the Backlight?
1)Press and hold the [MEM] key for 3 seconds
2)The [MEM] key will illuminate
3)Press the [MEM] key to set the desired backlight level
4)Press [CLEAR] or [ENTER] to exit
Spectra 1759MG - 30 - Programming Guide
Appendix A - Ademco CID Report Code List (Prog.)
If using the Ademco Contact ID Programmable code format, enter the 2-digit hexadecimal value from the table below (Prog. Value) into sections [160] to [213] to program the desired report codes. To enter a 0 value press the [FORCE] key.
CID#
Reporting Prog.
CodeValue
CID#
Reporting Prog.
CodeValue
CID#
Reporting Prog.
CodeValue
MEDICAL ALARMS - 100
203
Gate Valve Sensor2E
401
O/C by User5B
100
Medical Alarm01
204
Low Water Level2F
402
Group O/C5C
101
Pendant Transmitter02
205
Pump Activated30
403
Automatic O/C5D
102
Fail to Report In03
206
Pump Failure31
404
Late to O/C5E
FIRE ALARMS - 110
SYSTEM TROUBLES - 300 & 310
405
Deferred5F
110
Fire Alarm04
300
System Trouble32
406
Cancel60
111
Smoke05
301
AC Loss33
407
Remote Arm/Disarm61
112
Combustion06
302
Low System Battery34
408
Quick Arm62
113
Water Flow07
303
RAM Checksum Bad35
409
Keyswitch O/C63
114
Heat08
304
ROM Checksum Bad36
REMOTE ACCESS - 410
115
Pull Station09
305
System Reset37
411
Callback Request Made64
116
Duct0A
306
Panel Program Changed38
412
Success - Download Access65
117
Flame0B
307
Self-Test Failure39
413
Unsuccessful Access66
118
Near Alarm0C
308
System Shutdown3A
414
System Shutdown67
PANIC ALARMS - 120
309
Battery Test Failure3B
415
Dialer Shutdown68
120
Panic Alarm0D
310
Ground Fault3C
ACCESS CONTROL - 420
121
Duress0E
SOUNDER/RELAY TROUBLES - 320
421
Access Denied69
122
Silent0F
320
Sounder Relay3D
422
Access Report By User6A
123
Audible10
321
Bell 13E
SOUNDER RELAY DISABLES - 520
BURGLAR ALARMS - 130
322
Bell 23F
520
Sounder/Relay Disabled6B
130
Burglary11
323
Alarm Relay40
521
Bell 1 Disable6C
131
Perimeter12
324
Trouble Relay41
522
Bell 2 Disable6D
132
Interior13
325
Reversing42
523
Alarm Relay Disable6E
133
24-Hour14
SYSTEM PERIPHERAL TROUBLES - 330 & 340
524
Trouble Relay Disable6F
134
Entry/Exit15
330
System Peripheral43
525
Reversing Relay Disable70
135
Day/Night16
331
Polling Loop Open44
COMMUNICATION DISABLES - 550 & 560
136
Outdoor17
332
Polling Loop Short45
551
Dialer Disabled71
137
Tamper18
333
Exp. Module Failure46
552
Radio xmitter Disabled72
138
Near Alarm19
334
Repeater Failure47
BYPASSES - 570
GENERAL ALARMS - 140
335
Local Printer Paper Out48
570
Zone Bypass73
140
General Alarm1A
336
Local Printer Failure49
571
Fire Bypass74
141
Polling Loop Open1B
COMMUNICATION TROUBLES - 350 & 360
572
24-Hour Zone Bypass75
142
Polling Loop Short1C
350
Communication 4A
573
Burg. Bypass76
143
Expansion Module Failure1D
351
Telco Fault 14B
574
Group Bypass77
144
Sensor Tamper1E
352
Telco Fault 24C
TEST/MISC. - 600
145
Expansion Module Tamper1F
353
Long Range Radio4D
601
Manual Trigger Test78
24-HOUR NON-BURGLARY - 150 & 160
354
Fail to Communicate4E
602
Periodic Test Report79
150
24-Hour Non-Burglary20
355
Loss of Radio Supervision4F
603
Periodic RF Xmission7A
151
Gas Detected21
356
Loss of Central Polling50
604
Fire Test7B
152
Refrigeration22
PROTECTION LOOP TROUBLES - 370
605
Status Report to Follow7C
153
Loss of Heat23
370
Protection Loop51
606
Listen-in to Follow7D
154
Water Leakage24
371
Protection Loop Open52
607
Walk Test Mode7E
155
Foil Break25
372
Protection Loop short53
621
Event Log Reset7F
156
Day Trouble26
373
Fire Trouble54
622
Event Log 50% Full80
157
Low Bottled Gas Level27
SENSOR TROUBLES - 380
623
Event Log 90% Full81
158
High Temp28
380
Sensor Trouble55
624
Event Log Overflow82
159
Low Temp29
381
Loss of Super. -RF56
625
Time/Date Reset83
161
Loss of Air Flow2A
382
Loss of Super. - RPM57
626
Time/Date Inaccurate84
FIRE SUPERVISORY - 200 & 210
383
Sensor Tamper58
627
Program Mode Entry85
200
Fire Supervisory2B
384
RF xmtr. Low Battery59
628
Program Mode Exit86
201
Low Water Pressure2C
OPEN/CLOSE - 400
631
Exception Schedule Change87
202
Low CO22D
400
Open/Close5A
654
System Inactivity88
Spectra 1759MG - 31 - Programming Guide
Appendix B - Ademco CID Report Code List (All Codes)
System Event
Default Contact ID Report Code when option [3] is on in section [136]
System Event
Default Contact ID Report Code when option [3] is on in section [136]
Arming with Master Code (##)
3 4A1 - Close by user
Auxiliary supply trouble
1 3AA - System trouble
Arming with User Code (##)
3 4A1 - Close by user
Bell output current limit
1 321 - Bell 1
Arming with Keyswitch (##)
3 4A9 - Keyswitch Close
Bell absent
1 321 - Bell 1
Auto Arming
3 4A3 - Automatic Close
Clock lost
1 626 - Time/Date inaccurate
Arm with PC software
3 4A7 - Remote arm/disarm
Fire loop trouble
1 373 - Fire trouble
Late To Close
3 4A4 - Late to Close
Wireless Transmitter
Low Battery
1 384 - RF xmtr. low battery
No Movement
3 4A4 - Late to Close
Wireless Transmitter
Supervision Loss
1 381 - Loss of super. - RF
Partial arming
1 574 - Group bypass
Module fault
1 333 - Expansion module failure
Quick arming
3 408 - Quick arm
Printer fault
1 336 - Local printer failure
Fail to communicate with
central station
1 354 - Fail to communicate
Disarm with Master Code (##)
1 4A1 - Open by user
Wireless Transmitter
Low Battery
1 384 - RF xmtr. low battery
Disarm with User Code (##)
1 4A1 - Open by user
TLM trouble restore
3 351 - Telco 1 fault restore
Disarm with Keyswitch (##)
1 4A9 - Keyswitch Open
AC Failure restore
3 3A1 - AC loss restore
Disarm after alarm with
Master Code (##)
1 4A1 - Open by user
Battery Failure restore
3 3A9 - Battery test restore
Disarm after alarm with
User Code (##)
1 4A1 - Open by user
Auxiliary supply trouble restore
3 3AA - System trouble restore
Disarm after alarm with
Keyswitch (##)
1 4A9 - Keyswitch Open
Bell output current limit restore
3 321 - Bell 1 restore
Bell absent restore
3 321 - Bell 1 restore
Auto Arming Cancellation
1 4A5 - Deferred Open/Close
Clock programmed
3 626 - Time/Date Reset
Disarm with PC software
1 4A7 - Remote arm/disarm
Fire loop trouble restore
3 373 - Fire trouble restore
Disarm after an alarm with
PC software
1 4A7 - Remote arm/disarm
Wireless Transmitter
Low Battery
3 384 - RF xmtr. low battery
Wireless Transmitter
Supervision Loss
3 381 - Loss of super. - RF
Zone Bypassed (##)
1 57A - Zone bypass
Module fault restore
3 333 - Expansion module failure
restore
Zone alarm (##)
1 13A - Burglary Alarm
Printer fault restore
3 336 - Local printer failure restore
Fire alarm (##)
1 11A - Fire alarm
Fail to communicate with
central station
3 354 - Fail to communicate restore
Zone alarm restore (##)
3 13A - Burglary Alarm Restore
Fire alarm restore (##)
3 11A - Fire alarm Restore
Cold Start
1 3A8 - System shutdown
Test Report engaged
1 6A2 - Periodic test report
Panic 1 - Emergency
1 12A - Panic alarm
PC software communication
finished
1 412 - Successful - download access
Panic 2 - Medical
1 1AA - Medical alarm
Installer on site
1 627 - Program mode Entry
Panic 3 - Fire
1 115 - Pull Station
Installer programming finished
1 628 - Program mode Exit
Delinquency
1 654 - Inactivity
Recent closing
3 4AA - Open/Close
Global zone shutdown
1 574 - Group bypass
Duress alarm
1 121 - Duress
Zone shutdown (##)
1 57A - Zone bypass
Zone tampered (##)
1 144 - Sensor tamper
Zone tamper restore (##)
3 144 - Sensor tamper restore
AC Failure
1 3A1 - AC loss
Battery Failure
1 3A9 - Battery test failure
Spectra 1759MG - 32 - Programming Guide
Bus Module Connections
Printer Module (APR3-PRT1)Remove AC power and battery before adding APR3-PRT1 to the system. Do not connect any modules more than 76m (250ft) from the control panel. Only one Printer Module can be connected per Spectra control panel.A Green “Locate” LED: Remains illuminated during power upB Red “Watchdog” LED: Flashes to indicate proper operation. If there is a communication failure, the red LED will flash ON for one second and OFF for one second.C Red “TX” LED: Flashes when the Printer Module is transmitting data through the serial port only.D 25-pin Parallel Port: Connect the Printer Module’s 25-pin parallel port to any dot matrix printer. Note: The dot matrix printer must support a minimum of 80 columns.E 9-Pin Serial Port: Connect the Printer Module’s 9-Pin serial port to a dot matrix printer. Note: The dot matrix printer must support a minimum of 80 columns.F 9-Pin Serial Port: Connect the Printer Module’s 9-Pin serial port to a computer’s COM port to view the control panel’s events on the computer’s monitor. The events displayed on the monitor can then be printed through the printer connected to the computer.Spectra 1759MGControl PanelCommunication BusRX LED reserved for future usePress the “PRINT TEST” switch to perform a print testNot UsedABDEFCConnecting the PGM Output
Spectra 1759MG - 33 - Programming Guide
4-PGM Output Module (APR3-PGM4)
4-zone expansion Bus Module (SPC-ZX4 and APR3-ZX4)
Red “Watchdog” LED:Status: flashes once per second to indicate proper operation.Flash 1 second on and 1 second off: The module is experiencing a communicationfailure with the control panel. External Power Supply(Recommended: Paradox PSW817 1.75A Switching Power Supply)To Spectra 1759MG control panelNot UsedAny device such as a garage door opener, light or sirenCommunication BusRemove AC and battery from the control panel before adding the 4-PGM Output Module to the system. Do not connect the APR3-PGM4 more than 76m (250ft) from the control panel. Only one APR3-PGM4 can be connected per Spectra control panel.
Not UsedRed “WDG” LED:Status = Flashes to indicate proper operation.Flash 1 sec. on & 1 sec. off = Trouble and/or communication failure.Connect the detection devices to the module's input terminals exactly as shown in the Spectra 1759MG Reference & Installation Manual.Not UsedSpectra 1759MGcontrol panelCommunication BusRemove AC and battery power from the control panel before connecting the module to the communication bus. Do not connect the APR3-ZX4 or SPC-ZX4 more than 76m (250ft) from the control panel. Only one APR3-ZX4 or one SPC-ZX4 can be connected per Spectra control panel.Input terminal Z1 can be used as an anti-tamper switch input Option [2]: Section [650]Connecting the Anti-Tamper Switch
Spectra 1759MG - 34 - Programming Guide
Voice-assisted Arm/Disarm Bus Module (APR3-ADM2)
Green "PULSE"LED: Monitors the dialer. The LED will illuminate when the dialer is in use. When the dialer is not being used, the LED will remain off.Red “WATCHDOG” LED:Flashes once every second = normal.Flashes 1 second on & 1 second off = trouble and/or communication failure.Communication BusGround clampCold water pipe groundingHousehold telephoneRefer to Inset 1To Spectra 1759MG control panelSpectra 1759MG DialerNot UsedInset 1: Connecting the APR3-ADM2 PGM OutputPartial view of the APR3-ADM2External Power Supply(Recommended: Paradox PSW817 1.75A Switching Power Supply)Any device such as a garage door opener, light or sirenRemove AC and battery power from the control panel before adding the APR3-ADM2 module to the system. Do not connect the APR3-ADM2 more than 76m (250ft) from the control panel. Only one APR3-ADM2 can be connected per Spectra control panel.To reset the standalone code of the APR3-ADM2, you have to perform a hardware reset of the Spectra control panel.
Spectra 1759MG - 35 - Programming Guide
8-Zone Expansion Bus Modules (SPC-ZX8 and APR3-ZX8) Red “WDG” LED:Flash once every sec. = normal. Flash 1 sec. on & 1 sec. off = Trouble and/or communication failure.Not UsedInset 2Not UsedInset 1Refer to the Spectra 1759MG Reference & Installation Manual about connecting devices to the Expansion Input Terminals.Communication BusSpectra 1759MG control panelInset 1: Connecting the PGM outputInset 2: Anti-Tamper Switch ConnectionInput terminal Z1 can be used as an anti-tamper switch input.Option [2]: Section [650]Remove AC power and battery before adding a module to the system. Do not connect the APR3-ZX8 or SPC-ZX8 more than 76m (250ft) from the control panel. Only one SPC-ZX8 or APR3-ZX8 can be connected per Spectra control panel.
Spectra 1759MG - 36 - Programming Guide
Hardware Connections
Single Zone Inputs
Connecting Fire Circuits, Keyswitches and PGMs
Program the PGM with the “[PG]/[FNC1] Key was pressed” Activation Event so that the smoke detectors can be reset by pressing the [PG] or [FNC1] key. See Event Group # 5 on page 9.All 4-wire smoke detectors must be connected using the daisy chain configuration.Programming a Wireless Fire ZoneFire zones cannot be assigned to expansion zones. As a result, when installing a wireless smoke detector, the corresponding zone must be programmed as follows: 1)Enter [5] in the Zone Definition to define it as a 24Hr Burglary Alarm (see page 7).2)Disable [4] and enable [5] in Zone Options to set the zone’s alarm type to a pulsed Audible Alarm (see page 7).3)Disable [1] and [2] in Zone Options to disable the zone’s Auto Zone Shutdown and Bypass Enabled features (see page 7).Fire Circuits4-Wire InstallationControl Panel TerminalsKeyswitchPGM4)Change the zone’s report code from a Burglary Report Code (Prog. Value 11) to a Fire Report Code (Prog. Value 04). See Appendix A on page 30. If using Ademco Contact I.D., set the Contact ID Options from All Codes to Programmable (section [136] option [3] = OFF) and then enter the report code manually (see page 14).
Spectra 1759MG - 37 - Programming Guide
Alarm Relay and PGM Connections
Connecting More Than Two Keypads
If there are more than 2 keypads connected to the control panel and at least one keypad zone is being used, connect as shown and program as described in the Spectra 1759MG Reference & Installation Manual.
When a 1641 LCD keypad is connected to Spectra, the Keypad Zone Sending option (Option [2] key [1]) determines whether the status of the keypad zone will be transmitted to the control panel. Refer to the 1641 Installer’s Guide for more information. The Keypad Zone Sending option of the 1641 keypad must be enabled during the following conditions:
•If you are using both keypad zones and at least one is from a 1641 keypad.
•If you are using the keypad zones of other types of keypads, such as a 1686H 10-zone LED keypad, and the keypad zone definition of the 1641 keypad (keypad zone 1 or keypad zone 2; Option [2] key [3]) matches that of another connected keypad.
AC Power & Backup Battery Connections
Transformer Requirements Table
Transformer:
Amseco XP-1620 16VAC 20VA *
Recommended: 16VAC 40VA
UL: Basler BE156240CAA007
Spectra DC Power
Supply rated at:
1.2A
1.5A
Auxiliary Supply can provide a maximum of:
typ: 600mA
max: 700mA
typ: 600mA
max: 700mA
UL installations: typ. 200mA
Acceptable Battery Charge Currents (section [127] option [5])
350mA
350mA / 700mA
* Not verified by UL
PGMs When the device connected to a PGM is powered by:AUX+ terminal = must not exceed 700mAExternal power supply =PGM1 cannot exceed 150mAPGM2 cannot exceed 1AIf power supply's current limit is less than that of the PGM it is connected to, then the current consumption cannot exceed the power supply's current limit.PGM2 can be used as a strobe output. AUX+External power supplyAlarm Relay (5A) can be programmed to follow the BELL output or the Global PGMExternal Power SupplyAny device such as a strobe light or siren
Do not place a jumper across the zone and “BLK” input terminals of the keypads that are not using their keypad zones.A Door Contact or any other detection device.1686H(Using keypad zone)1686H(Not using keypad zone)1641 LCD Keypad(Not using keypad zone)Be sure to enable option [1] (”Keypad Zone Sending”) of option [2] (”Options”) in the 1641’s LCD Programming Mode.
Partial view of Spectra 1759MG control panelUL Warning: A 12Vdc / 7Ah battery is required to comply with UL fire requirements.Caution:Disconnect battery before replacing the fuse.Rechargeable BatteryUL/ULC - 12Vdc / 4Ah or 7AhWarning:Improper connection of the transformer may result in damage to the system.
Spectra 1759MG - 38 - Programming Guide
Spectra 1759MG PCB Layout
For UL and C-UL warnings, refer to the UL and C-UL Warnings section at the back of the Spectra 1759MG Reference & Installation Manual.
To connect the 5A Alarm Relay and the PGMs, refer to Alarm Relay and PGM Connections on page 37. To connect AC power, refer to AC Power & Backup Battery Connections on page 37.Refer to Single Zone Inputs on page 36Refer to AC Power & Backup Battery Connections on page 37.For the keypad’s zone, EOL and tamper configurations, refer to page 5.Warning: Do not connect keypads more than 76m (250ft) from the control panel.A Door Contact or any other detection device can be connected to the Keypad Zone.AUX Power Refer to transformer requirements on page 37 for Aux. Power Output. To connect additional wiring to auxiliary power, use the red (+) and black (-) keypad connectors. Auxiliary power will shut down if current exceeds 1.1A. If the auxiliary output is overloaded and is shut down, you must disconnect all loads from the output for at least 10 seconds before reconnecting any load back to the auxiliary output.Spectra KeypadsThe maximum number of keypads per installation is dependent on the auxiliary output, which cannot exceed 700mA.To provide maximum lightning protection we strongly recommend having separate earth connections for the dialer and zone ground terminals.To metallic enclosureGround clampAWG#14 single conductor solid copper wireCold water pipe groundingThe "BELL" output will shutdown if the current exceeds 3A.Communication BusWarning:Disconnect telephone line before servicing.Four pin connector can be used for quick installation of a Spectra keypad or Expansion Module.Warning:Do not cut, bend or alter the antennae and ensure that electrical wires do not cross over the antennae, as this may affect signal reception.Paradox Memory Key (PMC-3)Reset JumperAntennae"RX" LED:Flashes quickly whenreceiving signals from wireless devices."STATUS" LED:Flash once every second = normalFlashes ON 1 second and OFF 1 second = troubleAlways ON = panel is using phone lineFast flash 4 seconds after power up = installer lock enabled Warning:This equipment must be installed and maintained by qualified service personnel only.Connection for Self-Contained Bell/SirenThe sum of the current drawn from the BELL and AUX must be limited to 2.0A. Exceeding this limit will overload the panel power supply and lead to complete system shutdown.
Warranty
Paradox Security Systems Ltd. (“Seller”) warrants its products to be free from defects in materials and workmanship under normal use for a period of one year. Except as specifically stated herein, all express or implied warranties whatsoever, statutory or otherwise, including without limitation, any implied warranty of merchantability and fitness for a particular purpose, are expressly excluded. Because Seller does not install or connect the products and because the products may be used in conjunction with products not manufactured by Seller, Seller cannot guarantee the performance of the security system and shall not be responsible for circumstances resulting from the product’s inability to operate. Seller obligation and liability under this warranty is expressly limited to repairing or replacing, at Seller's option, any product not meeting the specifications. Returns must include proof of purchase and be within the warranty period. In no event shall the Seller be liable to the buyer or any other person for any loss or damages whether direct or indirect or consequential or incidental, including without limitation, any damages for lost profits stolen goods, or claims by any other party, caused by defective goods or otherwise arising from the improper, incorrect or otherwise faulty installation or use of the merchandise sold.
Notwithstanding the preceding paragraph, the Seller’s maximum liability will be strictly limited to the purchase price of the defective product. Your use of this product signifies your acceptance of this warranty.
BEWARE: Dealers, installers and/or others selling the product are not authorized to modify this warranty or make additional warranties that are binding on the Seller.
© 2002-2005 Paradox Security Systems Ltd. All rights reserved. Specifications may change without prior notice. One or more of the following US patents may apply: 6215399, 6111256, 5751803, 5721542, 5287111, 5119069, 5077549, 5920259 and 5886632. Canadian and international patents may also apply.
Spectra, Digiplex and Magellan are trademarks or registered trademarks of Paradox Security Systems Ltd. or its affiliates in Canada, the United States and/or other countries.
For technical support in Canada or the U.S., call 1-800-791-1919 for English or 1-866-912-0600 for French, Monday to Friday from 8:00 a.m. to 8:00 p.m. EST. For technical support outside Canada and the U.S., call 00-1-450-491-7444, Monday to Friday from 8:00 a.m. to 8:00 p.m. EST. Please feel free to visit our website at paradox.com.
780 Industriel Blvd., Saint-Eustache (Quebec) J7R 5V3 CANADATel.: (450) 491-7444 Fax: (450) 491-2313paradox.comPRINTED IN CANADA - 05/2006 1759MG-EP08